How Can We Help?
KCN-4ST-□ replace the timer operation

Question
I would like to replace the KCN-4ST- □ used for timer operation.
Please tell me the successor model and update procedure when updating to the current product.

Answer
The successor model will be the KT-V series.
Since there are differences in specifications, please check the following notes when replacing.
Replace
Model number comparison table
KCN-S series | KT-V series | remarks |
---|---|---|
KCN-4ST | KT-V4S | 4-digit AC power supply transistor output |
KCN-4ST-C | KT-V4S-C | 4-digit DC power supply transistor output |
Notes
1. The terminal block arrangement and setup menu items / display order are different between KCN-S and KT-V.
2. The key protection method is different.
3. The depth dimension of the product is different. (AC power supply: + 10mm, DC power supply: + 5mm)
4. Set the prediction output setting of KT-V to “zero”.
About operation
Output operation mode | Replaceability |
---|---|
Mode A: On-delay | ○ |
Mode B: Off delay | ○ |
Mode C: One Shot | ○ |
Mode D: Flicker | ○ |
Mode E: Accumulation | ○ |
Input connection method

Output connection method

Preset value
KCN-Both S / KT-V are set with each digit key.
Settings in setup mode
The setting order of the setup mode menu is different between KCN-S and KT-V.
In addition, some functions have changed to DIP SW settings.
Please set up referring to the figure below.

<For modes A / B / C / E>

Product
Related manual
Related keywords
Inquiry
technical support
Click here for inquiries by email
Click here for inquiries by email