SU series module position change

Question
Motion / high-speed counter modules (U-01PM, U-11PM, U-01SP, U-01Z) are used for the SU (D4) series.
Are there any precautions when changing the module configuration?

Reply
The RD / WT instruction may be used to read information from the relevant module in the ladder.
In this case, it is necessary to specify the slot for the corresponding module.
Search for RD / WT and change the base / slot specification in the LDR / LDS / LDW instruction before the module.
Precautions
Remote modules (U-02RM, U-03RM, U-23RM)
For remote modules, do not change the mounting slot.
This is because changing the mounting slot changes the I / O arrangement, increases the modification range of the user program, and affects the operation of the device.
This is because changing the mounting slot changes the I / O arrangement, increases the modification range of the user program, and affects the operation of the device.
Remote module (U-01KI “GENIUS”)
The D4-454 (DL454) CPU does not support U-01KI / KF.
Do not change to DL454 on equipment using U-01KI / KF.
Do not change to DL454 on equipment using U-01KI / KF.